transformer with a 10:1 ratio and rated at 60kVA, 2200/220V, 60Hz is used to step down the voltage of a distribution system. The low tension voltage is to kept constant at 220V. (a) What load Impedance connected to the low-tension side will be loading the transformer fully at 0.8 power factor (lag) ?       (b) What is the value of this impedance referred to the high tension side?

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.26P: A bank of three single-phase transformers, each rated 30MVA,38.1/3.81kV, are connected in Y- with a...
icon
Related questions
Question

A transformer with a 10:1 ratio and rated at 60kVA, 2200/220V, 60Hz is used to step down the voltage of a distribution system. The low tension voltage is to kept constant at 220V.

(a) What load Impedance connected to the low-tension side will be loading the transformer fully at 0.8 power factor (lag) ?       (b) What is the value of this impedance referred to the high tension side?

Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electric Motor Control
Electric Motor Control
Electrical Engineering
ISBN:
9781133702818
Author:
Herman
Publisher:
CENGAGE L