reactance’s of the alternator  during the periods of the subtransient, transient and steady state periods are following, Leakage reactance(XL)=0.16 ohm, Damper winding reactance(XD)= 0.28 ohm     Field winding reactance(Xf)=0.41 ohm and   Armature reactance (Xm)= 0.74 ohm. The value of the  steady state  reactance  during the  steady state   condition is                                                                        Steady state  Reactance  Answer

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter7: Symmetrical Faults
Section: Chapter Questions
Problem 7.3MCQ: The amplitude of the sinusoidal symmetrical ac component of the three-phase short-circuit current of...
icon
Related questions
Question

The reactance’s of the alternator  during the periods of the subtransient, transient and steady state periods are following,

Leakage reactance(XL)=0.16 ohm, Damper winding reactance(XD)= 0.28 ohm    

Field winding reactance(Xf)=0.41 ohm and   Armature reactance (Xm)= 0.74 ohm.

The value of the  steady state  reactance  during the  steady state   condition is                                                                     

 

Steady state  Reactance 

Answer
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning