Q. In a three phase 345 kV high-voltage overhead transmission line, the diameter of the conductors is given as 24 mm. a) Using the approximated maximum field calculation, determine the minimum distance between two phases (breakdown strength of air is 32 kV/cm, and k=0.9). b) In this configuration, if the distance between conductors (phases) is 1.2 m, at which voltage level there will be a flashover (discharge). c) In the same configuration, determine the maximum field strength if electrode separation is 1.60 m.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter4: Transmission Line Parameters
Section: Chapter Questions
Problem 4.18P: A 230-kV, 60-Hz, three-phase completely transposed overhead line has one ACSR 954 kcmil conductor...
icon
Related questions
icon
Concept explainers
Question
Q. In a three phase 345 kV high-voltage overhead transmission line, the diameter of the conductors is
given as 24 mm.
a) Using the approximated maximum field calculation, determine the minimum distance between two
phases (breakdown strength of air is 32 kV/cm, and k=0.9).
b) In this configuration, if the distance between conductors (phases) is 1.2 m, at which voltage level there
will be a flashover (discharge).
c) In the same configuration, determine the maximum field strength if electrode separation is 1.60 m.
A B
Maximum file size: 32MB, maximum number of files: 2
15:15
A 4 de 19.06.2021
MONSTER
NUM
Transcribed Image Text:Q. In a three phase 345 kV high-voltage overhead transmission line, the diameter of the conductors is given as 24 mm. a) Using the approximated maximum field calculation, determine the minimum distance between two phases (breakdown strength of air is 32 kV/cm, and k=0.9). b) In this configuration, if the distance between conductors (phases) is 1.2 m, at which voltage level there will be a flashover (discharge). c) In the same configuration, determine the maximum field strength if electrode separation is 1.60 m. A B Maximum file size: 32MB, maximum number of files: 2 15:15 A 4 de 19.06.2021 MONSTER NUM
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning