Consider a 60 Hz three-phase 141 km-long line with 2 of the 636 kcmil ACSR 26/2 conductors per phase. Assuming the line is loaded at its 75% capacity, calculate the per phase resistance for the liné. 1 mile 1.609 km

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter4: Transmission Line Parameters
Section: Chapter Questions
Problem 4.18P: A 230-kV, 60-Hz, three-phase completely transposed overhead line has one ACSR 954 kcmil conductor...
icon
Related questions
icon
Concept explainers
Question
Question 4
Consider a 60 Hz three-phase 141 km-long line with 2 of the 636 kcmil ACSR 26/2 conductors per
phase. Assuming the line is loaded at its 75% capacity, calculate the per phase resistance for the line.
1 mile = 1.609 km
Transcribed Image Text:Question 4 Consider a 60 Hz three-phase 141 km-long line with 2 of the 636 kcmil ACSR 26/2 conductors per phase. Assuming the line is loaded at its 75% capacity, calculate the per phase resistance for the line. 1 mile = 1.609 km
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning