6.4 The following test results are obtained for a 30, 25 kV, 750 MVA, 60 Hz, 3600 rpm, star-connected synchronous machine at rated speed. I(A) 1500 VLL. (kV) open-circuit test 25 I. (A) short-circuit test 10,000 VLL (kV) air gap line 30 (a) Determine the number of poles of the synchronous machine. (b) Determine the unsaturated and saturated values of the synchronous reactance in ohms and per unit. (c) The short-circuit test is performed at constant field current (1500 A) but at different speeds- 1000 rpm, 2000 rpm, 3000 rpm, and 3600 rpm. Determine the short-circuit current at these speeds. (d) Determine the field current if the synchronous machine delivers rated MVA to an infinite bus at 0.9 lagging power factor.

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.4P
icon
Related questions
Question

Solve part d only the others have been solved

 

6.4
The following test results are obtained for a 30, 25 kV, 750 MVA, 60 Hz, 3600 rpm, star-connected
synchronous
machine at rated speed.
It (A)
1500
VLL (KV)
open-circuit test
25
I. (A)
short-circuit test
10,000
VLL (KV)
air gap line
30
(a) Determine the number of poles of the synchronous machine.
(b) Determine the unsaturated and saturated values of the synchronous reactance in ohms and
per unit.
mi
(c) The short-circuit test is performed at constant field current (1500 A) but at different speeds-
1000 rpm, 2000 rpm, 3000 rpm, and 3600 rpm. Determine the short-circuit current at these
speeds.
(d) Determine the field current if the synchronous machine delivers rated MVA to an infinite bus
at 0.9 lagging power factor.
Тг
Transcribed Image Text:6.4 The following test results are obtained for a 30, 25 kV, 750 MVA, 60 Hz, 3600 rpm, star-connected synchronous machine at rated speed. It (A) 1500 VLL (KV) open-circuit test 25 I. (A) short-circuit test 10,000 VLL (KV) air gap line 30 (a) Determine the number of poles of the synchronous machine. (b) Determine the unsaturated and saturated values of the synchronous reactance in ohms and per unit. mi (c) The short-circuit test is performed at constant field current (1500 A) but at different speeds- 1000 rpm, 2000 rpm, 3000 rpm, and 3600 rpm. Determine the short-circuit current at these speeds. (d) Determine the field current if the synchronous machine delivers rated MVA to an infinite bus at 0.9 lagging power factor. Тг
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning